5 Before installation
26
Released media
Additives
The following products are currently released by Potterton:The following
products are currently released by Potterton:
"Full heating protection" from Fernox (www.fernox.com)
"Sentinel X100" from Guanako (www.sentinel-solutions.net)
"Jenaqua 100 and 110" from Guanako (www.jenaqua.de)
"Full protection Genosafe A" from Grünbeck
"Care Sentinel X100" from Conel (www.conel-gmbh.de)
Complete desalination
As a general rule, fully desalinated water can always be used, although
a pH value stabiliser is also required. The following products for produc­
ing fully desalinated water have been tested and approved:
"Complete desalination (VE) GENODEST Vario GDE 2000" from
Grünbeck (www.gruenbeck.de)
"Complete desalination cartridge SureFill" from Sentinel (www.senti­
nel-solutions.net)
more devices on request
Partial softening
The following products are currently released by Potterton:
Sodium ion exchanger "Fillsoft" from Reflex (www.reflex.de)
"Heifisoft" from Judo (www.judo-online.de)
"Heating water softening 3200" from Syr (www.syr.de)
"AQA therm" and "HBA 100" from BWT Wassertechnik (www.bwt.de)
"SoluTECH" from Cillit (www.gc-gruppe.de)
It must be ensured with an automatic blending device that the min. hard­
ness is not less than 6°dH .
See
The specifications of the manufacturer must be followed.
Further makes are currently undergoing testing. Please ask Potterton for
more information.
Caution
If non-approved products are used, the guarantee becomes void.
Antifreeze agent
Note
The use of antifreeze agents with Potterton gas condensing boil­
ers with aluminium heat exchangers.
The heat transfer medium (Lasacor® LS 1) offered for solar thermal sys­
tems is also used in heating systems (e.g. holiday houses) as an anti­
freeze agent, In the mixture supplied in the canisters (42 % Lasacor® LS
1, 58 % water), the freezing point ("crystal formation point" ) is -28°C. Due
to the lower thermal capacity and higher viscosity compared with water,
boiling noises can occur under unfavourable conditions.
For most heating systems, frost protection down to -28 °C is not required;
-15 °C is usually sufficient. The heat transfer medium must be diluted 2:1
with water to set this operating point. This mixing ratio has been tested by
Potterton in relation to its practical suitability for use with gas condensing
boilers.
Note
Up to a mixing ratio of 2.5:1 the heat transfer medium Lasacor®
LS 1 is approved as an antifreeze agent down to -15 °C for use
with Potterton gas condensing boilers.