Do Not Separate The Controller From The Mains; Electric Installation; Cable Dimensions; Maximum Cable Length - Honeywell SDC Operating Instructions Manual

Heating and district heating controller
Hide thumbs Also See for SDC:
Table of Contents

Advertisement

Safety Instructions

2.3 Do not separate the controller from the mains

2.4 Electric installation

2.5 Cable dimensions

2.6 Maximum cable length

2.7 Cable installation

rices and delivery to your door visit MyTub Ltd - 0845 303 8383 - www.mytub.co.uk - info@mytu
If this happens, the back-up battery will be unnecessarily
stressed. In addition, the frost protection functions of the
controller will be out of order.
Qualified personnel must carry out all electrical
connections.
1.5 mm² for all 230 V cable (power supply, burner,
pumps, actuators).
0.5 mm² for sensors, selectors, bus and analogue in- and
outputs.
Sensors selectors and analogue inputs
A maximum cable length of 200 meters is recommended.
Longer distances are possible but increase the risk of
interferences.
Relay outputs
Unlimited cable length.
Bus connections
A maximum cable length of 100 meters is strongly
recommended.
Cables for 230 V must be installed separate from low
voltage (sensor selector bus) cables.
5
SDC / DHC 43
EN2H-0220 GE51 R1005