16.2 Relationship Between The Condition Of The Mono bloc Unit And
Pressure And Electric Current
Heating Mode
Condition of the Mono bloc Unit
Electric current during
Low Pressure
High Pressure
operation
Water leakage or insufficient water flow
rate in the system
Excessive amount of refrigerant
Inefficient compression
Insufficient refrigerant
(gas leakage)
Mono bloc unit (refrigerant system) heat
exchange deficiency
Clogged expansion valve or Strainer
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is
started.