Menu #
(Hold Menu 8 Seconds)
32
35
50
65
66
* Setting the reversing valve to "O" or "B" is necessary for heat pump systems only. Please refer to the chart in
section 3.3 for your old thermostat's wiring.
On your OLD thermostat
• if you had a wire connected to "O" terminal, set reversing valve (menu # 20) valve as "O" at this step.
• if you had a wire connected to "B" terminal (and at the same time, no wire was connected to "O"), set reversing
valve as "B" at this step
• if you had a wire connected to "O/B" terminal, please call Customer Support at 877.654.9394.
Description
Aux Cycle Rate: how often the
auxiliary heat will turn on
Cool Cycle Rate: how often
the cooling will turn on
Compressor Lockout:
protects the compressor
from short cycling
Max Heat Limit: maximum set
point for heat mode
Minimum Cool Limit: minimum set
point for cool mode
Default Setting
(flashing icons)
SLO – slow
MEd
MEd – medium
FAS – fast
SLO – slow
MEd
MEd – medium
FAS – fast
On – 5 minute delay
OFF
OFF – no delay
99
47 to 99
45
45 to 97
Settings
(Press
or
)
21