Trane 7CONT624AS42DA User's Manual And Installation Instructions page 32

Touchscreen comfort control
Table of Contents

Advertisement

Installer's Setup Continued
Installer Settings allow the user to configure the equipment settings and customize how the control operates. To
access Installer Settings press the Menu button, then press Next until "Service" is displayed. Now press Select and
hold for 5 seconds until "Installer Settings" is displayed. Press Select again to enter Installer Settings menu. The
default setting will be shown in brackets. After each selection press Done to save changes.
Setting
Blower On Delay Cooling
Blower On Delay Cooling
Blower Off Delay Cooling
Blower Off Delay Cooling
Blower On Delay Heating
Blower On Delay Heating
Blower On Delay Heating
Blower Off Delay Heating
Blower Off Delay Heating
Blower Off Delay Heating
1st Stage Airflow Cool
2nd Stage Airflow Cool
1st Stage Airflow Heat
2nd Stage Airflow Heat
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
32
Installer's Guide
Range
Disabled, [Enhanced],
30 Second Delay,
1 Minute At 50%,
4 Minutes At 80%,
7.5 Minutes at 80%,
1 Minute At 50% 4 Minutes At 80%
[0] - 30 seconds
Disabled, 30 Seconds At 35%,
3 Minutes At 50%,
[1.5 Minutes At 50%],
30 Seconds At 50%,
45 Seconds At 100%,
1.5 Minutes At 100%
[0] - 90 Seconds
Disabled, [Enhanced],
30 Second Delay,
1 Minute At 50%,
4 Minutes At 80%,
7.5 Minutes at 80%,
1 Minute At 50% 4 Minutes At 80%
[0] - 30 Seconds
[0] - 60 Seconds
Disabled,
30 Seconds At 35%,
3 Minutes At 50%,
[1.5 Minutes At 50%],
30 Seconds At 50%,
45 Seconds At 100%,
1.5 Minutes At 100%
[0] - 90 Seconds
[0] - 90 Seconds
35% - 60%, [50%]
55% - 80%, [65%]
35% - 60%, [50%]
55% - 80%, [65%]
Airflow Settings
(Variable Speed indoor blower only) Select the cooling blower on
delay. Enhanced setting is 1 minute at 50% blower speed then 7.5
minutes at 80% blower speed and finally 100% blower speed.
(Non-Variable Speed blower only) Select the cooling blower on delay
(Variable Speed indoor blower only) Select the cooling blower off
delay
(Non-Variable Speed blower only) Select the cooling blower off delay
(Variable Speed indoor blower only) Select the compressor heating
blower on delay. Enhanced setting is 1 minute at 50% blower speed
then 7.5 minutes at 80% blower speed and finally 100% blower
speed.
(Non-Variable Speed blower only) Select the compressor heating
blower on delay
Select the hydronic heating blower on delay
(Variable Speed indoor blower only) Select the compressor heating
blower off delay
(Non-Variable Speed blower only) Select the compressor heating
blower off delay
Select the hydronic heating blower off delay
(2 compressor 2 stage only) Select 1st stage cooling airflow
(1 compressor 2 stage only) Select 1st stage cooling airflow
(2 compressor 2 stage only) Select 1st stage heating airflow
(1 compressor 2 stage only) Select 1st stage heating airflow
Description