Dunkirk 95M-200 Control Manual And Troubleshooting Manual page 25

Hide thumbs Also See for 95M-200:
Table of Contents

Advertisement

Display fl ashes fi rst digit E
Code
Reason for hard lockout
00
Flame detected on start-up
02
Ignition failed after 5 retries
03
Gas valve disconnected
04
Power lost after lockout
05
Internal control failure
06
Internal control failure
07
Internal control failure
11
Internal control error
12
Casting temperature switch open
13
Internal control failure
14
Internal control failure
15
Internal control failure
16
Internal control failure
17
Internal control failure
10 - USER INTERFACE QUICK REFERENCE
HARD LOCKOUT MODE
Boiler in hard lockout (requires manual RESET)
and last two digits (lockout code) (see below)
E
Code
18
Supply water temperature higher than 200°F
19
Return water temperature higher than 190°F
25
Outlet temperature increased too fast
28
No signal from blower; blower not running or defective blower motor
29
Blower signal not "0" when it should be
Max difference (b30) was too large for 20 successive times. Non
30
adjustable default max delta set to 100°F.
31
Outlet temperature sensor short circuit
32
Return temperature sensor short circuit
36
Outlet temperature sensor open circuit
37
Return temperature sensor open circuit
44
Internal control failure
60
Internal error reading parameters
61
Air fl ow circuit failure
65
Not enough blower driving force
Reason for hard lockout
25
xx