Panasonic CS-PS9JKT Service Manual page 53

Table of Contents

Advertisement

14.4.10 H28 (Outdoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature
sensor are used to determine sensor errors.
Malfunction Caused
Faulty connector connection.
Faulty sensor.
Faulty PCB.
Troubleshooting
When abnormality indication starts again
Check the connector connection:
Turn off the power
Check the connector connection
Is the connector connection normal?
Check the outdoor heat exchanger temperature sensor:
Plug out connector from the outdoor unit PCB
Measure the resistance of the outdoor heat exchanger
temperature sensor
Is the measured resistance of the outdoor heat exchanger
temperature sensor matches the value specified in its
characteristic chart?
Sensor (Thermistor)
Characteristics
70
1 Outdoor Air Sensor
2 Outdoor Heat Exchanger
60
Sensor
50
40
1
30
2
20
10
0
-10
0
10
20
Temperature (ºC)
YES
YES
30
40
50
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
No
Connector poor contact
Correct the connection
Defect in outdoor heat exchanger
temperature sensor
No
Replace the outdoor heat exchanger
temperature sensor
Defect in outdoor unit PCB
Replace the outdoor unit PCB
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-ps12jktCu-ps9jktCu-ps12jkt

Table of Contents