Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use it's own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
A firestop is required whenever the vent penetrates a wall, floor, or ceiling (passes through framing
members). Horizontal vent less than 48" (1219mm) above the fireplace must use the Travis Firestop
(sku 250-00747 - it incorporates a 4" (102mm) clearance above, 1"( 25mm)clearance below and to
the sides of the vent). Other penetrations only require a 1" (25mm) clearance and may use a
standard firestop (make sure the required 1" (25mm) clearance is met).
Always use the high-wind termination (if available from the vent manufacturer).

Vent Clearances

The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Sides
Above
Below Horizontal or 45° Section
Vertical Termination
Use a roof flashing and storm collar
whenever passing through the roof
Use a firestop whenever
passing through a ceiling
Use a support box
on exposed vent

Altitude Considerations

This heater has been tested at altitudes ranging from sea level to 6,000 feet (1800M). In this testing we have
found that the heater, with its standard orifice, burns correctly with just an air shutter adjustment.
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.
© Travis Industries
Installation
(for qualified installers only)
Before 48" (1219mm)
Rise
1" (25mm)
4" (102mm)
1" (25mm)
Required Firestop
Min. 1"
25mm
4141208
After 48" (1219mm)
Rise
1" (25mm)
1" (25mm)
1" (25mm)
Horizontal
Termination
Min. 4" (102mm)
1" (25mm) if a minimum 48"
(1219mm) above the
fireplace.
Min. 1"
Min. 1"
25mm
25mm
100-01397