3.3   System Settings
The AC Output Voltage and System Earthing parameters
must only be changed by a competent electrical engineer.
The following settings are available to users through the RCC-03 controls. Further
details available on request.
Basic Settings
Maximum current of AC Source
Restore default settings
Inverter
AC Output Voltage
Danger! Adjustments should only be
made by qualified personnel
AC In & Transfer
§
Maximum current of AC Source (Mode
1: Three Phase)
Maximum current of AC Source (Mode
2: Single Phase Mode & Mode 3: Three
Phase With L1 Backup)
Aux. Contact 1
Operating Mode
Combination of Events
Contact active with fixed time schedule
Program 1
Page 22
CYGHPG12-24-User-Manual-v1.6.indd
W A R N I N G
Min: 2
Default: 50
Max: 50
Yes -> Confirm
Min: 220 V
Default: 230 V
Max: 245 V
Min: 2
Default: 50
Max: 50
Min: 2
Default: 21
Max: 50
Automatic (Default)
Reverse Automatic
Manual On
Manual Off
Any (Default)
And
Day of week
Start hour
End hour
AC In & Transfer Current settings
§
provide adjustment to allow
charging sources with various
capacities to be used with the unit.