Input Line Cords
The following input line cords are for connecting the PDU to appropriate power
circuits. This may include for example, the wall or floor outlets to provide power to
the PDU. See the
0U PDU Attached line cord and plugs
line cord plug.
PDU P/N
Feature
Code
46M4143
5927
Specifications
The following table are specifications for the 46M4143 0U 12 C19 / 12 C13 PDU.
Specifications
PDU Part Number
Feature Code
Input Line Cord Type
Phase
Type
Outlets types
Power Capacity*
Power Limit per Outlet
Grouping
Power Limit per Group 20A
Power Limit per PDU
Power
Monitoring/Switching
U Space
Grounding Screw
* For the purpose of this table, you can consider 1 VA = 1 Watt.
88
Line Cord
Line Cord Description
P/N
Attached
Attached 3.0 meter line cord IEC-309 3P+N+G
32A (32A / Phase) 380-415VAC Three Phase
Wye 96A Total Circuit Capacity
46M4143
5927
Attached
3 phase
32A/ 220V-240V, 380-415V
twelve IEC C13 & twelve IEC C19
22080VA@230V
Each C13 outlet is limited to10A
Each C19 outlet is limited to 16A
Two C13 + two C19 outlets per breaker
Four C13 + four C19 outlets per phase
96A
No/No
Side pocket
Yes on front panel
section for a picture of the