0U Pdu Attached Line Cord And Plugs; Attached 16A 3Ph Cord (Iec309 3P+N+G) - Lenovo System x PDU Technical Reference

Table of Contents

Advertisement

.

0U PDU Attached line cord and plugs

This section covers all the plugs on each line cord for the 1U Rack PDUs which
include line cords:

Attached 16A 3ph Cord (IEC309 3P+N+G)

Attached 32A 1ph Cord (IEC309 P+N+G)
Attached 32A 3ph Cord (IEC309 3P+N+G)
Attached 16A 3ph Cord (IEC309 3P+N+G)
IEC-309 3P+N+G 3.0 meter 16A, 3P5W plug (Type 516P6W)
32A (32A / Phase) 380-415VAC Three Phase Wye
48A Total Circuit Capacity
Only a receptacle or a connector is needed to mate with the plug on the PDU input
line cord. See the
Additional Plug Information
further details on IEC309.
Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N
HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N
HBL532C6W
Used with:
Basic PDU:
46M4122 –
0U 24 C13 PDU
170
on page
191
in this document for