DPI Enterprise PDU+ C13
This section discusses the 39M2816 DPI Enterprise PDU+ C13. This section is broken
up into the following sections.
Quick Specs
•
Front and Back View and Outlets
•
Input Line Cords
•
Specifications
•
Accessories kit
•
Racking
•
Installation and Maintenance Guide
•
Quick Specs
The following tables are quick specs for the 39M2816 PDU+. For additional
information, refer to the
PDU 39M2816 + Line Cord 40K9611
Type
Outlets types
Power Capacity
Power Limit per PDU 96A
Phase
PDU 39M2816 + Line Cord 40K9612
Type
Outlets types
Power Capacity
Power Limit per PDU 32A
Phase
103
Specifications
section.
32A / 380V-415V
twelve IEC C13
22080VA @ 230V
Three phase
32A / 220V-240V
twelve IEC C13
7360VA @ 230V
Single phase