Higher Voltage Dc Pdu Line Cord And Hard Wiring; Hvdc Line Cord And Plug - Lenovo System x PDU Technical Reference

Table of Contents

Advertisement

.

Higher Voltage DC PDU Line cord and hard wiring

The following section discusses the Higher Voltage DC (HVDC) line cord and hard
wiring.

HVDC Line cord and plug

90A@240-380VDC cable 4.3 meter
Pig-tail termination (hardwired, no plug).
Three stranded copper conductors, each with a cross section of 25 sq. mm.
Used with:
HVDC PDU:
44T0966 –
1U Higher Voltage PDU
There is no plug on the HVDC PDU and it must be hardwired. See Figure
picture of the cord.
The cord must be connected to an appropriately wired and grounded high-voltage dc
power source by a licensed electrician, following the local electrical codes or
requirements.
The PDU conductors are connected to a high-voltage dc power source as described
in the table.
Wired Color
Yellow
Blue
Brown
Figure 110: HVDC PDU cord for hard wiring
174
Function
Earth / Ground wire
Negative DC Voltage wire
Positive DC Voltage wire
110