Prestige Series Installation and Operator's Manual for IBM Applications (3000 VA) Uncontrolled Copy
1. Place the conduit through the access hole on the junction box
(see Figure 10). Connect the exposed conduit wires to the
corresponding compression terminals (see the following table).
Tighten the compression terminals with a screwdriver.
2. Pivot the REPO receptacle guard out of the way, plug the REPO
plug/receptacle UPS connector into the REPO receptacle on the
UPS rear panel and twist the connector in place (see Figure 5
on page 37).
Access Hole
for Conduit
Figure 10. Optional REPO Cord Junction Box
Power Cable Terminations
Wire Function
REPO
L1
L2
Ground
*
Suggested wire size is #18-AWG (0.75 mm
NOTE
The REPO function activates when L1 and L2 are shorted together.
Mounting Holes
Terminal Block
Terminal
Terminal Wire
Position
Size Rating*
TB1-4
12 - 22 AWG
TB1-5
2
2
(4 - 0 mm
(4 - 0 mm
)
)
TB1-6
2
) 75
C copper wire minimum.
Installation
Plug/Receptacle
UPS Connector
Three Foot Cord
Tightening Torque
Entrelec
Phoenix
Contact
3.5 - 5.3 lb in
5.6 - 6.8 lb in
45