Ups With Ppdm Startup - 3Com Powerware Uninterruptible Power System Prestige Series Installation And Operator's Manual

3000 va, 200-240v
Table of Contents

Advertisement

Installation
42
Powerware

UPS with PPDM Startup

To start up the UPS:
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
"UPS Monitoring" on page 52 for instructions.
2. Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position.
3. Steps 4 through 8 are for changing the output voltage. The
output voltage is factory-configured for 230V. If you do not
need to change the output voltage, skip to Step 9.
Use the following table to select the correct output voltage
according to your PPDM.
PPDM Model Number
5-15R PPDM 208: 120/208
5-15R PPDM 208: 120/240
5-15R PPDM 208: 120
5-15R PPDM 240: 120/240
5-15R PPDM 240: 120
5-15R/6-15R PPDM: 208
5-15R/6-15R PPDM: 240
IEC 320-C13 PPDM
*
The UPS output voltage should be set according to local mains voltage.
Prestige Series Installation and Operator's Manual for IBM Applications (3000 VA) Uncontrolled Copy
®
UPS Voltage Selection*
208
208
208
Set to 220V for 110/220V PPDM output
Set to 230V for 115/230V PPDM output
Set to 240V for 120/240V PPDM output
Set to 220V for 110V PPDM output
Set to 230V for 115V PPDM output
Set to 240V for 120V PPDM output
208
240
Set to 220V for 220V PPDM output
Set to 230V for 230V PPDM output
Set to 240V for 240V PPDM output

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Powerware Uninterruptible Power System Prestige Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Powerware prestige series

Table of Contents