Feature & Operation
6-2-10 Low Temperature Release
G AT COOLING MODE
N If the temperature of indoor heat exchanger is below -1°C for over 6minutes, the outdoor fan turns off.
N If the temperature of indoor heat exchanger increase over 5°C during the first protection function, the first freezing protection
function is released and the outdoor fan turns on.
N If the temperature of indoor heat exchanger increase over 0°C during 6 minutes counting, 6 minutes counter is cleared.
N If the temperature of indoor heat exchanger maintains for a minute at -4°C during the 6 minutes counting, the compressor is
switched off.
N If the compressor is off by Low Temperature. Restart within 5 minutes is impossible.
N Operation pattern
Indoor Heat exchanger Temp.(˚C)
5[˚C]
0[˚C]
-1[˚C]
Compressor
Outdoor FAN
Indoor FAN
40
6min
6min
6min
COUNT
COUNT
COUNT
ON
ON
OFF
6min
ON
ON
Setting Fan speed
Low temp.
release
ON
3sec
OFF
OFF
"LL"
*LL = Low FAN speed – 35rpm
Low temp.
release
OFF
ON
2sec
ON
Setting Fan speed
Samsung Electronics