Samsung AS09HPBN Training Manual page 40

Hide thumbs Also See for AS09HPBN:
Table of Contents

Advertisement

6-2-9 Overload protection control
G AT HEATING MODE
N If indoor heat exchanger temp. is over 53°C, outdoor fan turns off.
N If indoor heat exchanger temp. is over 60°C, outdoor compressor stops and Indoor fan speed is low.
N The indoor fan, outdoor fan and compressor will resume normal operation when the indoor heat exchanger temperature drops
below 50˚C.
Samsung Electronics
Indoor Heat Exchanger Temp.
60˚C + offset
53˚C + offset
50˚C + offset
ON
Compressor
ON
Outdoor Fan
Indoor Fan
Setting Speed
ON
3min Delay
OFF
ON
OFF
2Sec
Low Speed
*offset = 0, 1, 2, 3˚C
Feature & Operation
Time
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As12hpbnAs09hpaAs12hpa

Table of Contents