ESS Introduction and Planning
Table 21. ESS power cable connectors
Power cable
Power cable Description (See
Feature Code
Notes 1 and 3.)
9801, 9986
1-phase, 50/60 Hz 50 A (See
Notes 4 and 10.)
9802
1-phase, 50 Hz (See Notes 4
and 10.)
9803
1-phase, 50/60 Hz, 60 A (See
Note 4.)
9851, 9987
3-phase, 50/60 Hz, 50 A (See
Notes 5 and 10.)
9988, 9854
3-phase, 50/60 Hz, 60 A (See
Notes 5 and 10.)
9852
3-phase, 50 Hz, (See Notes 5
and 11.)
9853
3-phase, 50/60 Hz, 60 A (See
Note 5.)
Notes:
1. All power cables are rated at 600 V ac except power cables for Japan, which are 250
V ac. Single-phase power cables have 2 poles and 3 wires. Three-phase power cables
have 3 poles and 4 wires.
2. Connector and receptacle types indicated are Russell Stoll except types for Japan,
which can use any manufacturer.
3. All power cables are 4.7 m (14 ft) long except Chicago, which is 2 m (6 ft) long.
4. Not available on the Model E20 or F20 or the expansion enclosure.
5. Not available on the Model E10 or F10.
6. Install IEC309 receptacle in a metal-backed box with the green wire ground-connected
to the grounding lug within the box. Ensure continuity between the box and the metallic
shielding of the liquid-tight conduit.
7. The 7428-78 in-line connector must have the appropriate JPA adapter included in the
assembly to ensure continuity between the connector housing and the metallic
shielding of the liquid-tight conduit.
8. IBM recommends that you attach these in-line connectors to a liquid-tight,
metallic-shielded conduit, using adapter C75 for 1.89 cm (3/4-in.) conduit, or using C10
for 2.54 cm (1-in.) conduit.
9. These receptacles require back box 3711A.
10. For low-voltage, single phase installations (200 V to 240 V), IBM recommends a
minimum rated circuit breaker of 40 amperes, and not to exceed the wire rating of the
facility.
11. For low-voltage, three phase installation (200 V to 240 V), IBM recommends a
minimum rated circuit breaker of 25 amperes, and not to exceed the wire rating of the
facility.
12. For high-voltage, single phase installations (380 V to 415 V), IBM recommends a
minimum rated circuit breaker of 20 amperes, and not to exceed the wire rating of the
facility.
13. For high-voltage, three phase installations (380 V to 415 V), IBM recommends a
minimum rated circuit breaker of 15 amperes, and not to exceed the wire rating of the
facility.
In-line Connector
Receptacle (See
(See Note 2.)
Note 2.)
9C53U0 (See Note
9R53U0W (See
8.)
Note 9, 10, and
12.)
No connector
Hard wire (See
note 10 and 12.)
Not used
360R6W (See
Note 6, 10, and
12.)
9C54U0 (See Note
9R54U0W (See
8.)
Note 9, 11, and
13.)
7428-78 (See Note
7324-78 (See note
7.)
11 and 13.)
No connector
Hard wire (See
note 11 and 13.)
Not used
460R9W (See
Note 6, 11, and
13.)