Vitocom 100, Type Lan1 - Viessmann VITODENS 200-W Technical Manual

Gas condensing boilers 17.0 to 150.0 kw as multi boiler system up to 900.0 kw
Table of Contents

Advertisement

Control units
(cont.)
Using the inputs and outputs allows up to 5 functions to be ach-
ieved:
1 switching output (floating changeover contact)
■ Central fault message issue (only with the Vitotronic 100, type HC1B
and Vitotronic 200, type HO1B)
■ Switching a feed pump to a substation
■ Switching the DHW circulation pump (only with the Vitotronic 200,
type HO1B)
1 analogue input (0 to 10 V)
■ Specifying set boiler water temperature
3 digital inputs
■ External operating mode changeover for 1 to 3 heating circuits (only
with the Vitotronic 200, type HO1B, and the Vitotronic 300-K,
type MW2B)
■ External blocking
■ External blocking with central fault message
■ Minimum boiler water temperature demand
■ Fault messages
■ Short term operation DHW circulation pump (only with the
Vitotronic 200, type HO1B, and Vitotronic 300-K, type MW2B)
■ Signalling reduced operation for one heating circuit (only for the
Vitotronic 300-K, type MW2B)
5
5 8

Vitocom 100, type LAN1

■ Without communication module
Part no. Z011 389
■ With communication module
Part no. Z011 224
For remote control of heating systems via internet and IP networks
(LAN) with DSL router.
Storage combi boiler for wall mounting.
For system operation with Vitotrol app or Vitodata 100.
Functions when operating with Vitotrol app:
■ Remote control of up to three heating circuits of a heating system
■ Setting operating programs, set values and time programs via
iPhone, iPad or iPod with Retina display, with operating system
iOS 4.3/5
■ Scanning system information
■ Displaying messages on the Vitotrol app user interface
Note
For further information see "www.vitotrol-App.info".
Functions when operating with Vitodata 100:
Remote monitoring of all heating circuits in a heating system:
■ Forwarding messages via email to PC/smartphone (email client
function required)
■ Forwarding messages via SMS to mobile phone/smartphone or fax
(via chargeable internet service Vitodata 100 fault management)
VIESMANN
68
0
1 8
Specification
Rated voltage
Rated frequency
Rated current
Power consumption
Rated breaking capacity of the relay
output
Safety category
IP rating
Permissible ambient temperature
– during operation
– during storage and transport
Remote control:
Setting operating programs, set values, time programs and heating
curves
Configuration:
Configuration is automatic.
If the DHCP service is enabled, no settings are required at the DSL
router.
Standard delivery:
■ Vitocom 100, type LAN1 with LAN connection
■ Connecting cables for LAN and communication module
■ Power cable with plug-in power supply unit
■ Vitodata 100 fault management for a duration of three years
On-site requirements:
The communication module must be installed in the control unit.
Before commissioning, check the system requirements for communi-
cation via the IP networks (LAN).
Internet connection with data flat rate (flat rate independent of time
and volume).
Note
For information on registering and using the Vitotrol app and
Vitodata 100, see "www.vitodata.info".
230 V~
50 Hz
2 A
4 W
2(1) A 250 V~
I
IP 20 D to EN 60529
ensure through appropriate
design/installation
0 to +40 °C
Installation in living spaces or
boiler rooms
(standard ambient conditions)
–20 to +65 °C
VITODENS 200-W