Radio Clock Receiver; Vitocom 100, Type Gsm; Extension Kit For One Heating Circuit With Mixer With Integral Mixer Motor - Viessmann VITODENS 200-W Technical Manual

Gas condensing boiler 3.8 to 35.0 kw
Table of Contents

Advertisement

Control units
(cont.)
2 0

Radio clock receiver

Part no. 7450 563
For receiving the DCF 77 time signal (location: Mainflingen near Frank-
furt/Main).
Radio controlled setting of time and date.
Install on an outside wall, facing the transmitter. The reception may be
reduced by metallic elements in the building structure, e.g. steel rein-
forced concrete, neighbouring buildings and sources of electro-mag-
netic interference, e.g. HV and public transport lines.
Connection:
■ 2-core lead, length up to 35 m with a cross-section of 1.5 mm
per)
■ Never route this lead immediately next to 230/400 V cables.

Vitocom 100, type GSM

■ Without SIM card
Part no. Z004594
■ With contract SIM card for the operation of the Vitocom 100 via
mobile phone
Part no. Z004615
Note
For further information regarding the conditions of contract, see the
Viessmann pricelist.
Functions:
■ Remote switching via GSM mobile phone networks
■ Remote scanning via GSM mobile phone networks
■ Remote monitoring via SMS to 1 or 2 mobile phones
■ Remote monitoring of additional systems via digital input (230 V)
Configuration:
Mobile phones via SMS
Standard delivery:
■ Vitocom 100 (subject to order with or without SIM card)
■ Power supply cable with Euro plug (2.0 m long)
■ GSM aerial (3.0 m long), magnetic foot and adhesive pad
■ KM BUS cable (3.0 m long)
On-site requirements:
Good reception for GSM communication of the selected mobile phone
operator.
Total length of all KM BUS subscriber cables up to 50 m.

Extension kit for one heating circuit with mixer with integral mixer motor

Part no. 7301 063
KM BUS subscriber
Components:
■ Mixer PCB with mixer motor for Viessmann mixer DN 20 to 50 and
R ½ to 1¼
■ Flow temperature sensor (contact temperature sensor), lead length
2.2 m, fully wired, for specification see below
VITODENS
Comprising:
■ Wall mounting base with fixing materials
■ 5 m long cable with plugs
■ Cover for the control unit aperture on the boiler
6 6
4 1
2
(cop-
0
7 2
1 3
Specification
Rated voltage
Rated frequency
Rated current
Power consumption
Protection class
Protection
Function
Permissible ambient temperature
– during operation
– during storage and transport
On-site connection
Fault input DE 1
■ Connecting plug for the heating circuit pump
■ Power cable (3.0 m long)
■ BUS cable (3.0 m long)
The mixer motor is mounted directly onto the Viessmann mixer DN 20
to 50 and R ½ to 1¼.
230 V ~
50 Hz
15 mA
4 W
II
IP 41 to EN 60529; safeguard
through appropriate design
and installation
Type 1B to EN 60 730-1
0 to +55 °C
Installation in living spaces or
boiler rooms (standard ambi-
ent conditions)
-20 to +85 °C
230 V~