Section 4
D. Remove the white vinyl water distribution
tubing
Disconnect the hose from the water pump outlet.
Disconnect the hose from the dump valve (the tubing
pressure fits - pull tubing into evaporator
compartment).
E. Remove the water pump
Disconnect the water pump power cord.
POWER
CORD
WATER
PUMP
DO NOT SOAK
WATER PUMP
MOTOR IN
CLEANER OR
SANITIZER
SOLUTIONS
Water Pump Removal
Loosen the screws securing the pump mounting
bracket to the bulkhead.
Lift the pump and bracket assembly off the screws.
Part Number 000001114
F. Remove the water level probe
Loosen the screw that holds the water level probe in
place. The probe can easily be cleaned and sanitized
at this point without proceeding to step 2.
If complete removal is required, disconnect the wire
lead from the control board inside the electrical
control box.
LOOSEN
SCREWS
WATER
TROUGH
Step 7 Mix a solution of cleaner and warm water.
SV1618
Depending upon the amount of mineral buildup, a larger
quantity of solution may be required. Use the ratio in the
table below to mix enough solution to thoroughly clean
all parts.
Solution Type
Cleaner
Step 8 Use 1/2 of the cleaner/water mixture to clean all
components. The cleaner solution will foam when it
contacts lime scale and mineral deposits; once the
foaming stops use a soft-bristle nylon brush, sponge or
cloth (NOT a wire brush) to carefully clean the parts.
Soak parts for 5 minutes (15 - 20 minutes for heavily
scaled parts). Rinse all components with clean water.
SCREW
WATER
LEVEL
PROBE
Water Level Probe Removal
Water
1 gal. (4 l)
16 oz (500 ml) cleaner
Maintenance
WIRE
LEAD
ICE
MACHINE
SIDE
PANEL
SV1621
Mixed With
4-3