INSTALLATION
Minimum Alcove Clearance and Clearance to Combustible Materials
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
Small F1100S
Large F3100L
A combustible fl oor must be protected by a non-combustible material (like tile,
concrete board, or certifi ed to UL-1618 or as defi ned by local codes) extend-
ing beneath the heater and a minimum of 8" from each side and minimum
16" from the front face of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.
Minimum Overall Width (X) of Floor
Protector for all installations:
Small Stove
Large Stove
NOTE: In Canada, fl oor protection must extend 18" to the front and 8" to each side of the stove.
Minimum Overall Depth (Y) of Floor Protector
Unit
Small F1100S
Large F3100L
*The rear clearance to combustibles is less than 6" (152mm), for corner installations the rear corners may be angled to take advantage of the
closer clearances.
10
Unit
with Airmate
with Rear Defl ector
with Airmate
with Rear Defl ector
Floor Protection
F1100S
38"
F3100L
42"
with Airmate
38"
with Rear Defl ector
38"
with Airmate
43"
with Rear Defl ector
43"
From
From Flue
Unit
Center-line
G
H
I
11"
7"
23"
13"
5"
25"
16"
9.5"
30"
(not approved for Alcove)
8
Residential
Residential
"C" Vent
Close Clearance
Y
Z
Y
6"
37"*
6"
37"*
6"
43"
6"
43"
Min.
Width
J
K
13.5"
46"
11.5"
50"
16"
60"
8
Mobile Home
Close Clearance
Z
Y
Z
5"
38"
6"
5"
37"*
5"
6"
43"
6"
6"
43"
6"
Regency F1100/F3100 Freestanding Woodstove
Min.Hearth
to Rear Wall
L
39"
37"
46.5"
8
8
Alcove
Y
Z
38"
6"
37"*
5"
43"
6"
n/a
n/a