F3100 Wood Stove
206
Wood Stoves
F3100 Large Stove
Minimum Clearance To Combustible
Materials
Please read the section below carefully as clearances depend on whether
the airmate or the rear heat defl ector is installed on the stove.
Measurements "From Unit" are from the top plate of the stove to a side
wall or to a corner, and from the rear heat shield to a back wall.
Residential Installation "C" Vent (Single Wall)
Unit
F3100
with Airmate
with Rear Defl ector
From Unit
From Corner
A
B
C
D
18"
12"
8.5"
32"
20"
14"
10.5"
34"
June 2007 Regency Product Specifi cations Book
From Vent
centerline
E
F
18.5"
22"
20.5"
24"