Maintenance
Figure 12-4 Burner Assembly - Models 601 - 801

Check flame signal

1. At high fire the flame signal shown on the display should
be at least 10 microamps.
2. A lower flame signal may indicate a fouled or damaged
flame sense electrode.
electrode does not improve, ground wiring is in good
condition, and ground continuity is satisfactory, replace
the flame sense electrode.
3. See Section 3 - Troubleshooting in the Knight XL Service
Manual for other procedures to deal with low flame
signal.

Review with owner

1. Review the Knight XL User's Information Manual with
the owner.
2. Emphasize the need to perform the maintenance
schedule specified in the Knight XL User's Information
Manual (and in this manual as well).
3. Remind the owner of the need to call a licensed
contractor should the boiler or system exhibit any
unusual behavior.
4. Remind the owner to follow the proper shutdown
procedure and to schedule an annual start-up at the
beginning of the next heating season.

Cleaning boiler heat exchanger

For recommended materials; including brush, appropriate
extension(s), refractory cover, and detailed instructions see
Table 12B - Heat Exchanger Cleaning Kits.
1. Shut down boiler:
• Follow the "To Turn Off Gas to Appliance" instructions
for the boiler in Section 10 - Startup.
• Do not drain the boiler unless it will be exposed to
freezing temperatures. If using freeze prevention fluid
in system, do not drain.
2. Allow time for the boiler to cool to room temperature if
it has been firing.
76
AIR ARM
BURNER
GASKET
SCREWS
(QTY. 5)
If cleaning the flame sense
Installation & Operation Manual
3. Remove the nuts securing the heat exchanger access cover
to the heat exchanger and set aside.
4.
Remove the heat exchanger access cover, burner, and
gas/air arm assembly.
The boiler contains ceramic fiber materials.
WARNING
Use care when handling these materials per
instructions in the Service Manual. Failure
to comply could result in severe personal
injury.
5. Remove the condensate hose from the heat exchanger end.
Connect a field supplied 3/4" diameter hose to a drain pan.
Using field supplied means, cover the refractory in the back
of the combustion chamber of the heat exchanger.
6. Use a vacuum cleaner to remove any accumulation on the
boiler heating surfaces. Do not use any solvent.
7. Brush the heat exchanger while dry using a nylon bristle
brush. Caution: DO NOT use a metal brush. Re-vacuum
the heat exchanger.
8. Finish cleaning using a clean cloth dampened with warm
water. Rinse out debris with a low pressure water supply.
9. Allow the heat exchanger to thoroughly dry.
10. Remove the field supplied rear refractory cover from the
back of the combustion chamber of the heat exchanger and
reassemble.
11. Close isolation valves on piping to isolate boiler from
system. Attach a hose to the boiler drain and flush boiler
thoroughly with clean water by using purging valves to
allow water to flow through the water make-up line to the
boiler.
12. Perform start-up and check-out procedures in the Check
Flame and Combustion - Section 10 - Startup on pages 57
and 59 of this manual.
13. Replace the access cover and restore boiler to operation.
Table 12B Heat Exchanger Cleaning Kits
Kit
Model
Number
Number
CTN20005
MSC20083*
400
KIT30063
MSC20084
MSC20086
CTN20005
501
MSC20083*
-
KIT30064
MSC20085
801
MSC20086
* Do NOT use a metal brush. Only use the
CAUTION
kit provided brush or an equivalent
replacement nylon brush.
Part
Component
Description
Rear Refractory Cover
Nylon 4" Wheel Brush*
3mm Allen Wrench
1/4" x 24" Drill Extension
Rear Refractory Cover
Nylon 4" Wheel Brush*
1/4" x 12" Drill Extension
1/4" x 24" Drill Extension