Operating information
Ramp delay
For systems with lower flow, the SMART SYSTEM can limit
the firing rate (when enabled) when a space heating call for
heat starts, or when switching from a DHW call for heat to
a space heating call for heat. There are six (6) limits that
can be programmed, as well as six (6) time intervals
corresponding to each limit. The sixth limit will also limit
the firing rate for the rest of the call for heat.
Gradient limiting
If during operation of the boiler the outlet water
temperature is rising too quickly, the control will reduce the
firing rate to its lowest setting.
Outdoor air reset
If an outdoor air sensor is connected, the control module
will calculate the set points of the three (3) space heating
demands based on the programmed reset curves. The
installer can change the slope of the reset curves by several
adjustable parameters. The user can limit the maximum
set point for the system using the space heating set points.
Boost function
If outdoor air reset is active, and any space heating demand
has been active continuously for a set period of time (time
adjustable by installer) and there has been no DHW
demands, the control will increase the set point of that
demand by a fixed number of degrees (adjustable by
installer).
This process will continue until the space
heating demand ends, the set point reaches the
programmed set point or a maximum of 20 increases has
occurred. Once the system heat demand is satisfied, the set
point will revert to the value determined by the reset curve.
Night setback
The controller may be programmed to reduce the space
heating and DHW set points during certain times each
week.
Seven different start and stop times may be
programmed for the space heating setback and seven start
and stop times for the DHW setback.
Flame current support
To prevent nuisance shutdowns when the boiler is firing at
minimum rates, the control will increase the firing rate
when the flame signal drops too low.
62
Installation & Operation Manual

Protection features

Outlet
temperature,
temperature rise limiting
The outlet temperature is monitored by the boiler outlet
temperature sensor. When the outlet temperature exceeds
185°F, the unit will reduce the fan speed. If the outlet water
temperature exceeds 195°F (90°C) the control will shut the unit
down until it cools off.
The control module monitors the flue temperature by a sensor
located in the flue exhaust. If the flue temperature exceeds
215°F (102°C) the control will reduce the maximum fan speed.
If the flue temperature exceeds 240°F (115°C) the control will
shut the unit down. The unit will restart automatically once the
flue temperature drops 25°F (-4°C) and the minimum off time
has expired.
The control monitors the temperature difference between the
inlet and the outlet sensor. If this difference exceeds 55°F
(13°C) the control will reduce the maximum fan speed. If the
temperature difference exceeds 60°F (15°C) the control will
shut the unit down. The unit will restart automatically once the
temperature difference has dropped below 55°F (13°C) and the
minimum off time has expired.
Freeze protection
DO NOT install the boiler in a room likely to freeze.
The following integral feature of the SMART SYSTEM control
module provides some protection for the boiler only -- not for
the system.
The SMART SYSTEM control module provides
freeze-up protection as follows when the boiler
water temperature drops below 45°F (7°C):
Below 45°F (7°C), the boiler and system pumps
operate constantly.
Below 37°F (3°C), the boiler turns on.
Boiler and pumps turn off if boiler water
temperature rises above 45°F (7°C).
Lower temperatures may be programmed for
systems with anti-freeze solutions.
When system return temperatures are
NOTICE
maintained
condensation will form on the inside of the
boiler jacket causing some internal sheet
metal components to rust.
This feature of the SMART SYSTEM
CAUTION
control module does not eliminate the
possibility of freezing.
must
installation and maintenance practice to
prevent freeze potential for the boiler and
system.
flue
temperature,
below
the
dew
The installation
still
use
recognized
and
point,
design,

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

801Knight xl 501Knight xl 601Knight xl 701

Table of Contents