Raypak B0507 Owner's Manual And Installation Instructions page 47

Table of Contents

Advertisement

Sub
Menu
Menu
Sensor Type
Correction of measured value
Start of display
InP
InP1
End of display
Filter time constant, analog input 1
Temperature unit
Controller type
Operating Action
Cntr
Lower set point limit
Upper set point limit
ConF
Alarm function
Limit value
AF
Switching differential
Response to Out Of Range
RWF55 Adjustment Procedures
Notes to all RWF55 adjustment procedures:
If a button is not pressed within 180 seconds during any thermostat adjustment procedure, and 'ENTER'
has not been pressed to save the new value, the thermostat display will revert to show the current probe
temperature without modifying the selected parameter. If this occurs it will be necessary to reprogram the
selected parameter.
The thermostat will operate as normal whilst performing any thermostat adjustment procedure.
Checking or Adjusting RWF55 Set Point
Press and release the (▼) button, the current set point temp (green display) will start
1.
flashing.
Press and release (▲) or (▼) to adjust the set point to the required value.
2.
Press and release 'ENTER' to confirm the new setting. The green display will stop flashing
3.
and the new set point will be displayed.
Checking or Adjusting RWF55 'User (OPr) Level' Parameters
Note: For Raypak standard programming only user level parameter SP 1 is able to be adjusted, other parameters
may be available but are display only at this level.
Press and release 'ENTER', 'OPr‟ appears in the lower display.
1.
Press and release 'ENTER'; 'SP 1‟ and the current set point are displayed.
2.
Press and release 'ENTER'; 'SP 1‟ will start flashing
3.
Press and release (▲) or (▼) button to enter the value for SP 1 as shown in the „Raypak Setting‟ column of
4.
the
"RWF 55 User Level Parameters"
Press and release 'ENTER' to accept the new setting. „SP 1‟ will cease flashing and the new set point will be
5.
displayed.
Press and release (▲) or (▼) button, „InP1‟ and the current water temperature will be displayed. This is
6.
information only to confirm the sensor is reading the correct water temperature.
Press 'ESC' for more than 2 seconds, the display will revert to show the probe and set point temperatures.
7.
RWF55 Configuration (ConF) Level Parameters
Parameter
table on page 46.
Display
Value Range
1....19 digit
SEn1
-1999....+9999 digit
OFF1
-1999....+9999 digit
SCL1
-1999....+9999 digit
SCH1
0.0.....100.0 digit
dF1
Unit
CtYP
CACt
-1999....+9999 digit
SPL
-1999....+9999 digit
SPH
0....12 digit
FnCt
-1999....+9999 digit
AL
HYSt
ACrA
47
TEMPERATURE CONTROL
Raypak Setting
1....2 digit
1....2 digit
0....1 digit
0....999.9
0....1 digit
6
0
0
100
1
1
1
1
0
95
0
0
1
0