Raypak B0507 Owner's Manual And Installation Instructions page 12

Table of Contents

Advertisement

INSTALLATION
The water heater must be mounted on a level fire proof base such as a concrete slab, concrete plinth, steel plate
etc. Water heaters must NOT be installed on carpeting.
The front of the water heater must not be obstructed by any gas or water piping, electrical conduits, etc.
SAFE TRAY
Where damage to property can occur in the event of the water heater leaking, the water heater must be installed in
a safe tray. Construction, installation and draining of a safe tray must comply with AS/NZS 3500.4 and all local
codes and regulatory authority requirements. AS/NZS 3500.4 also has particular requirements when a safe tray
must be installed.
FIRE RESISTANT MATERIALS
Fire resistant materials should comply with the requirements of AS 5601 or AS/NZS 5601.1 Appendix C. If in doubt,
seek advice from your material supplier or your local regulator.
CLEARANCES
The distances set out in the following table should be observed.
Minimum Clearances from:
Rear
Water Side
Front
Non Water Side
Ceiling
Note: For External units . If the unit is to be installed in front of wall, ESV inspectors will require the outer rim of the
cowl to be 1 metre from the wall.
The normal water heater design is with the water pipe entry from the left hand side. For servicing purposes allow
the required clearance as shown in the table in front of the water heater for burner tray removal.
INDOOR INSTALLATION
The correct draught diverter must be fixed to the top
of the water heater (models 507 – 1922) and
connected to a properly constructed flue
discharge the combustion products outside the
building. The flue must be self supporting and not
impose a load on the water heater. Use a slip joint or
similar to allow for disconnection and to enable the
water heater top panel and/or draught diverter to be
removed for servicing. There must be a vertical rise
of 600 mm from the draught diverter before
changing direction. The flue design and installation
must comply with AS/NZS 5601 or AS/NZS 5601.1.
NOTE: Reduction of the flue diameter or alteration to
the draught diverter may void the water heater
warranty.
The water heater is to be installed at ground or floor
level and must stand vertically upright. There are
also special requirements in AS 5601 or AS/NZS
5601.1 for water heaters installed in a garage, an
enclosed space or other locations. Remember all
local authorities have regulations about putting water
heaters into roof spaces.
Non Combustible materials (mm)
507 - 1922
2004 - 4224
150
600
750
600
1200
to
12
Combustible Materials (mm)
507 - 1922
300
600
600
600
1200
750
600
600
1200
1200
2004 - 4224
600
600
1200
600
1200