TEMPERATURE CONTROL
TEMPERATURE ADJUSTMENT – MODULATING MODELS (RWF55 ELECTRONIC THERMOSTAT)
All modulating models are fitted with an RWF55 electronic
thermostat which has the following features:
The thermostat display shows the current tank
sensor (probe) temperature and the current set point
temperature during normal operation.
The thermostat has parameters that control system
operation. Refer to
46.
Thermostat set point, parameters, parameter options
and parameter settings (or parameter information)
can be viewed or adjusted. Refer to
Adjustment"
on page 47.
The burner symbol will illuminate green whenever the
thermostats internal relay is closed (call for heat).
If the thermostat detects a faulty temperature sensor
the thermostat will show a fault code on the display.
Refer to
"Diagnostic Features Of RWF55 Controller"
on page 8.
An Ambient Air Compensator (not supplied) can be connected. Refer to
49.
RWF55 Parameters
The RWF55 thermostat has parameters that control hot water system operation. Under normal conditions,
including a power outage, parameter settings do not require adjustment; however, parameter settings may be
altered to „fine tune‟ a system to suit a particular installation.
The parameter menu is comprised of a process data level parameter menu, a parameter level parameter menu and
a configuration level parameter menu.
The following tables detail all available parameters, each parameter range and the default (factory) setting of each
parameter. Parameters MUST be set to the grey shaded „Raypak Setting‟ column for the hot water system to
operate correctly.
Set point 1
(1)
Set point is user definable and may differ to setting shown in „Raypak Setting‟ column.
Proportional band
Derivative time
Integral action time
Dead band (neutral zone)
Actuator running time
Switch on threshold burner
Switch off threshold stage II
Upper switch off threshold
Response threshold
"RWF55 Parameters"
RWF55 User (OPr) Level Parameters
Parameter
RWF55 Parameter (PArA) Level Parameters
Parameter
on page
"RWF55
Display
SP1
Display
Pb.1
dt
rt
db
tt
HYS1
HYS2
HYS3
q
46
Modulating down
Modulating up
"Ambient Air Compensator"
Value Range
Raypak Setting
SPL – SPH
Value Range
Raypak Setting
0.1....999.9 digit
0....9999 seconds
0....999.9 digit
0....999.9 digit
0.0 to -1999.9 digit
0.0 to -199.9 digit
0.0....HYS# digit
0.0....999.9 digit
0.0....999.9
on page
(1)
78
20
15
60
3
30
-3
0
4
0.0