Raypak B0507 Owner's Manual And Installation Instructions page 37

Table of Contents

Advertisement

COMMISSIONING
COMMISSIONING THE WATER HEATER
THE WATER HEATER MUST BE COMMISSIONED AND CERTIFIED IN ACCORDANCE WITH AS 3814,
APPENDICES A-F.
"Operating the Water Heater"
Refer to
"Component Checks and Adjustment Procedures"
Refer to
heater.
OPERATIONAL CHECKS
Turn on water heater and circulation pump and verify flow switch operation (refer to
Heater" on page 39).
Test the operation of the water heater with no gas flow to confirm its operation up to lockout stage and then
turn off the power to the water heater.
Open the gas isolation valve and switch on power to the water heater.
With the main burner lit and at high fire, check the gas inlet pressure (refer to
page 40).
Check the water heater gas train and components for gas leaks using soapy water. NOT A NAKED FLAME
Set the burner gas pressure to that shown on the rating label (refer to
page 40).
Make a visual check of the burners. The flame should be blue with a well defined pattern. A yellow or floating
flame indicates restricted air openings or an incorrect burner gas pressure setting.
Verify that the high limit thermostat is operating and set correctly (refer to
on page 42).
For indoor installations check that the flue is drawing correctly.
Check operation of the water pressure relief valve.
It is normal for the water heater to produce some smoke and possibly condensation for the first thirty (30)
minutes of operation from new (refer to
If the installation is for a closed loop water source heat pump, perform the
Pump Commissioning Procedure"
Explain to the responsible officer the functions and operation of the water heater.
Warning: Upon completion of the installation and commissioning of the water heater, leave this guide with the
responsible officer. DO NOT leave this guide inside of the cover of the water heater, as it may interfere with the
safe operation of the water heater or ignite when the water heater is turned on.
section on page
39
for instructions on filling and lighting the water heater.
on page
"Safety
Precautions" on page 35).
on page 38.
37
40
for instructions on adjustment of the water
"To Turn on the Water
"Gas Inlet Pressure Check"
"Burner Gas Pressure Adjustment"
"High Limit Thermostat Adjustment"
"Closed Loop Water Source Heat
on
on

Advertisement

Table of Contents
loading