Intermittent Pump Operation
Where pump operation is intermittent, a remote thermostat must be fitted in the system and a pump run on timer is
required to remove residual heat from the water heater and prevent nuisance tripping of the high limit thermostat. A
run on timer is available as an optional kit (Rheem part No 56076874).
Minimum Pump Inlet Pressure
Circulating pumps require a minimum inlet pressure in order to operate without cavitation. For the minimum
pressure requirements for Grundfos UPS series pumps, refer to the
Grundfos Series Pumps"
system characteristics and need to be calculated. Contact your pump supplier for more information.
WATER FLOW RATE AND PRESSURE DROP
10°C Rise
l/sec
kPa
2.75
18
2.87
6
3.58
10
4.06
14
4.66
22
5.26
27
5.38
29
6.09
43
6.31
44
6.31
46
6.31
47
6.31
49
6.31
49
6.31
55
6.31
55
6.31
58
6.31
58
10.63
45
12.06
48
12.62
49
12.62
49
12.62
53
12.62
50
12.62
57
12.62
54
12.62
60
12.62
57
table on page 18. Minimum pressure requirements for TP series pumps depend on
15°C Rise
l/sec
kPa
1.83
9
1.91
3
2.39
4
2.71
6
3.11
8
3.5
12
3.58
12
4.06
18
4.22
18
4.38
24
4.54
24
4.78
30
5.02
30
5.68
50
5.68
50
5.68
58
5.68
58
7.09
18
8.04
20
8.44
27
9.56
29
9.95
35
11.47
38
11.79
53
12.62
54
12.62
57
12.62
57
"Minimum Pressure Requirements for
17
CONNECTIONS – PLUMBING
20°C Rise
l/sec
kPa
1.37
1.43
1.79
2.03
2.33
2.63
2.69
3.05
3.17
3.28
3.4
3.58
3.76
4.42
5.54
4.9
5.14
5.32
6.03
6.33
7.17
7.47
8.6
8.84
10.03
10.09
11.47
5
3
3
4
5
7
7
10
11
13
15
16
18
27
30
31
39
12
12
17
18
21
23
30
30
42
42