CHAPTER 2 Preparing for Main Unit Installation

2.7 Confirming the Supplied Parts

2.7
Confirming the Supplied Parts
Confirm that the delivered parts match the shipping list provided with the main unit.
If any of the parts listed in the shipping list or performance records are missing, incorrect, or damaged, contact the
distributor where you purchased your product, or your sales representative.
Note
-
If you also purchased optional modules for installation, such as additional memory modules or PCI Express cards, first
confirm that the main unit functions normally before mounting the optional modules in the main unit.
-
License key must be kept by customer. If you apply the RAID software license, when you will exchange SAS array
controller card at the reason for the failure of it, you will need to input the license key.
2.8

Mounting the Main Unit in a 19-inch Rack

The PRIMEQUEST2000 series server is mounted for use in a 19-inch rack. For details on mounting, see Appendix A
Racks in the PRIMEQUEST2000 Series Hardware Installation Manual (CA92344-0535).
2.9

Connecting the Power Cables

This section describes how to connect the power cables.
You need to connect the power cables to outlets with ground terminals.
Remark
The main unit and PCI_Box are designed to operate with a power supply facility that supports grounded wiring. Do not
connect the main unit and PCI_Box to a power supply facility that does not provide grounded wiring. To determine the type
of power supply in your building, contact the building manager or a qualified electrician.
Note
If PSU configuration is redundant and power cables are connected first, there is a case the Alarm LED (Amber LED) on
OPL is turned on. Also, "Configuration error in excess unit" message is logged in System Event Log. This message does
not indicate a failure of the power supply. Please set Power Feed Mode or PSU Redundant Mode in MMB-Web UI.
Operations
1.
Confirm with an engineer specializing in electricity that the input power satisfies power requirements. For details on
the power requirements, see 1.3 Installation Specifications in the PRIMEQUEST2000 Series Hardware Installation
Manual (CA92344-0535).
2.
Confirm that the power cables are connected to the AC inlets of the main unit and PCI_Box. Also confirm that the
power cables are secured with the AC cord clamps for the AC inlets on the main unit.
6