Joints; Mounting The Boiler; Fitting The Flue System; Choice Of Flue - Biasi RIVA ADVANCE HE M110B.24SM/C User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for RIVA ADVANCE HE M110B.24SM/C:
Table of Contents

Advertisement

6.5

Joints

Functions
Gas, c.h. return, c.h. flow
D.c.w. inlet
D.h.w. outlet
Pressure relief valve
Condensate drain
sizes in mm o.d.
6.6

Mounting the boiler

• Take the protective caps off the boiler
pipework.
• Thoroughly clean the connections.
• Mount the boiler on its bracket.
• Fix the gas cock K (¾") to the boiler using
the ¾" gaskets (Fig. 6.3)
• Fix the ø 22 mm pipe M to the gas cock K
using the ¾" gaskets (Fig. 6.3)
• Repeat the above procedure for the d.c.w.
inlet utilising the ½" cold water inlet valve
N, the ø 15 mm copper tail O with its con-
nection nut and two ½" gaskets.
• Fix the ø 22 mm copper tails L with the ¾"
connection nut and a ¾" gasket.
• Fix the ø 15 mm copper tail P with the ½"
connection nut and a ½" gasket.
M
L
P
Fig. 6.3
• Connect the pipe Q (Fig. 6.4) from the
pressure relief valve to the safety dis-
INSTALLATION
Pipe sizes
(o.d)
ø 22
ø 15
ø 15
ø 15
ø 25 (plastic)
O
L
N
K
charge pipework.
• Fit the condensate drain 15 (Fig. 6.4) in
the air brake connected to the drainage
pipework. See also section "Condensate
drain" to page 31.
15
Fig. 6.4
6.7

Fitting the flue system

Refer to the assembly instructions con-
tained within the chosen flue kit packaging
for the correct assembly and installation.
In general, it has to be taken in considera-
tion that the horizontal sections of the flue
pipe must have an horizontal sloping not
less than 1.5 deg. (25 mm per metre) to-
wards the boiler.
In the standard horizontal flue kit (Fig. 6.6
A) the flue pipe is angled within the air duct
therefore the air duct must be horizontally
installed.
If one or more extensions have to be used
they must be adequately supported so that
there is no sag in the flue pipe and a mini-
mum fall of 1,5 deg. (25 mm per metre) over
the whole length towards the boiler is en-
sured.
6.8

Choice of flue

The following flue kits are available for con-
necting to the boiler:
Q
- 37 -