Positioning Information / Installation - Wolf CGG-1K-24 Installation And Operating Instructions Manual

Gas fired wall mounted boiler
Table of Contents

Advertisement

General
- Determine the installation location for the gas fired boiler;
maintain the specified minimum clearances (see the r.h.
diagram).
- Fit the installation template (paper poster) supplied to the
wall.
- Transfer the fixing hole and connection positions marked
on the installation template to the wall (e.g. with a power
drill).
- Remove the installation template.
- Drill Ø 12 mm holes for the mounting bracket and secure the
bracket using the rawl plugs and screws supplied. (Before
securing the bracket, check that the rawl plugs are suitable
for the wall construction.)
- Remove the casing lid of the gas fired boiler. For this, pivot
the control unit lid down, hook in the r.h. and l.h. turn buckle,
undo the bottom of the casing lid and unhook at the top.
- Hang the gas fired boiler with the hook-in brace on the back
of the boiler into the mounting bracket.
l.h. turnbuckle
Fig.: Opening the turnbuckle
The gas fired boiler may only be installed in rooms that are
protected from frost.
During the boiler installation ensure that all fixings
are sufficiently strong to carry its weight. Also con-
sider the wall consistency, otherwise gas or water
may escape which could lead to explosions and
flooding.
NB
During the boiler installation, ensure that no
contaminants (e.g. drilling swarf) enter the gas
fired boiler otherwise faults may develop.
The combustion air supplied to the boiler must
be free from chemicals, e.g. fluoride, chlorine or
sulphur. Such materials are contained in sprays,
solvents and cleaning agents. Under the most un-
favourable conditions, these may lead to corrosion,
even in the flue gas system.
Balanced flue gas fired boilers must only be
installed in a room that complies with the appro-
priate ventilation requirements. Otherwise there
is a risk of asphyxiation or poisoning. Read
these installation and operating instructions
before installing the gas fired boiler. Also take
the technical guide into consideration.
3062087_1108

Positioning information / Installation

r.h. turnbuckle
Fig.: Installation template
Installation inside a cupboard
For installation of the gas fired boiler inside a cupboard note
the following:
- Remove the back wall of the cupboard
Minimum clearance between the gas fired boiler and the cup-
board sides 25 mm.
40
Never install the gas fired boiler on the back wall of
the cupboard, as this component may not be sub-
stantial enough to carry the boiler weight. This would
create the risk of water and gas leaks which in turn
would result in a risk of explosion and flooding.