Ras-18Nkhd-E4 / Ras-18Uah-E4 - Toshiba RAS-24NKHD-E4 Service Manual

Split wall type
Table of Contents

Advertisement

5-2. RAS-18NKHD-E4 / RAS-18UAH-E4

Cooling
0.39 m
Heating
(Connecting pipe)
∅12.7
O.D.:12.7 mm
P
Packed valve
(∅12.7)
Gas container connection (Reinstall etc.)
Heating
Cooling
4-way valve
Heating Cooling Compressor
Cooling
Heating
50 Hz
Standard
Heating
High temperature*1
Low temperature
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Indoor unit
Evaporator
Cross flow fan
2JS350D5DA02
Accumulator
Condenser
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
pressure P
exchanger interchanging
(MPaG)
1.70
2.10 ~ 2.26
1.20
0.40
0.50
0.30
– 22 –
FILE NO. SVM-05016
T
Packed valve
(∅6.35)
Capillary tube
∅0.8x400 s
Capillary tube
∅2.0x600 s
Refrigerant
R22 1.17 kg
Mark (
) means check points of Gas Leak
Fan speed
(indoor)
pipe T (°C)
45. . 0
High
49.0 ~ 58.0
Low
34.0
High
10.0
High
15.0
High
1.0
Low
0.49 m
(Connecting pipe)
∅6.35
O.D.:6.35 mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
20/–
7/6
27/–
24/18
20/–
–10/–10
27/19
35/24
32/23
43/26
21/15
21/15