Safety Devices - Fujitsu AUU7RLF Design & Technical Manual

2/3/4 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

11.

SAFETY DEVICES

Circuit protection
Fan motor protection
Compressor protection
Refrigerant circuit protection Pressure switch (1)
*Pressure switch (2) : For control device
Protection form
Current fuse (MAIN PCB)
Current fuse
(NEAR THE TERMINAL)
Temperature Thermistor
Temperature Thermistor
- (03 - 39) -
Model
AOU24RLXFZ
250V 3.15A
250V 5A
250V 10A
OFF: 302 ± 27°F
OFF: 150 ± 15 °C
ON: 248 ± 27 °F
ON: 120 ± 15 °C
OFF: 230 ± 4 °F
OFF: 110 ± 2 °C
ON: 176 ± 4 °F
OFF: 609 ± 15 PSI
OFF: 4.2 ± 0.1 MPa
ON: 464 ± 22 PSI
ON: 3.2 ± 0.15 MPa
ON: 80 ± 2 °C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents