Fujitsu AUU7RLF Design & Technical Manual page 157

2/3/4 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

12) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
Function number
49
*00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
*01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
13) Room temperature control for wired remote controller sensor
Refer to Function 95, before performing this setting.
Depending on the installed environment, correction of the wired remote controller temperature
sensor may be required. Select the appropriate control setting according to the installed
environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Function number
92
93
(For cooling)
(For heating)
14) Heat Insulation condition (building insulation)
Heat insulation conditions differ according to the installed environment.
Standard insulation "00" allows system to rapidly respond to the cooling or heating load
changes. High insulation "01" is when the heat insulation structure of the building is high and
does not require system to rapidly respond to cooling or heating load changes.
When High insulation "01" is selected;
 Overheating (overcooling) is prevented at the start-up.
„ A ll room temp. control settings (Function 30, 31, 92, 93) will reset to No correction [0.0°F
(0.0°C)].
Function number
95
NOTE:
When changing Function 95, perform this setting before other Room temp. control settings (Function 30, 31, 92,
93). If Funtion 95 is not set first, Room temperature control settings (Function 30, 31, 92, 93) will be reset and you
must re-do them again.
Setting value
00
01
Setting value
Setting description
00
No correction 0.0°F(0.0°C)
01
No correction 0.0°F (0.0°C)
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
Setting value
Setting description
00
Standard insulation
01
- (01 - 153) -
(  ... Factory setting)
Setting description
Disable
Enable
(  ... Factory setting)
-1°F (-0.5°C)
-2°F (-1.0°C)
-3°F (-1.5°C)
-4°F (-2.0°C)
-5°F (-2.5°C)
-6°F (-3.0°C)
-7°F (-3.5°C)
-8°F (-4.0°C)
+1°F (+0.5°C)
+2°F (+1.0°C)
+3°F (+1.5°C)
+4°F (+2.0°C)
+5°F (+2.5°C)
+6°F (+3.0°C)
+7°F (+3.5°C)
+8°F (+4.0°C)
(  ... Factory setting)
High insulation
More Cooling
Less Heating
Less Cooling
More Heating