Fujitsu AUU7RLF Design & Technical Manual page 127

2/3/4 rooms type
Hide thumbs Also See for AUU7RLF:
Table of Contents

Advertisement

ERROR STATUS OUTPUT
Compact
Cassette
Connector
An air conditioner error status signal can be output.
Circuit diagram example
z
Indoor unit
control PC board *1
Connector
1
2
*1 PC board of Communication kit is used for Wall mounted (ASU9RLS2, ASU12RLS2, ASU15RLS2, ASU7RLF1,
ASU9RLF1, ASU12RLF1) type.
*2 Make the distance from the PC board to the connected unit within 10m.
Error
Error status
Normal
ON
Output signal
OFF
Parts (Optional)
z
Compact
Cassette
Parts name
Model name
Compact
Cassette
Parts name
Model name
* For operating the EXTERNAL OUTPUT function, the wall mounted type (ASU9RLS2, ASU12RLS2, ASU15RLS2,
ASU7RLF1, ASU9RLF1, ASU12RLF1) requires the communication kit (UTY-TWBXF/UTY-XCBXZ2) in addition to the
wire (UTY-XWZXZ5).
ASU7RLF
Slim Duct
ASU9RLF
ASU12RLF
Ex.)Relay unit
24V DC
V
10m *2
Signal
Locally purchased
ASU7RLF
Slim Duct
ASU9RLF
ASU12RLF
ASU7RLF
Slim Duct
ASU9RLF
ASU12RLF
- (01 - 123) -
Wall Mounted
ASU9RLS2
ASU7RLF1
ASU12RLS2
ASU9RLF1
ASU15RLS2
ASU12RLF1
CNB02
Connected unit
Ex.)Display
Relay
power
supply
Wall Mounted
ASU9RLS2
ASU7RLF1
ASU12RLS2
ASU9RLF1
ASU15RLS2
ASU12RLF1
External connect kit
UTY-XWZXZ5
Wall Mounted
ASU9RLS2
ASU7RLF1
ASU12RLS2
ASU9RLF1
ASU15RLS2
ASU12RLF1
Communication kit
UTY-TWBXF UTY-XCBXZ2
Floor
AGU9RLF
ASU18RLF
AGU12RLF
ASU24RLF
AGU15RLF
CN21
Relay spec.:
Max.24V DC, 10mA to less
than 500mA.
Floor
AGU9RLF
ASU18RLF
AGU12RLF
ASU24RLF
AGU15RLF
External
connect kit
UTY-
XWZXZ5
Floor
AGU9RLF
ASU18RLF
AGU12RLF
ASU24RLF
AGU15RLF