NFS Supra

6 Specifications

General
NFS Supra control panels (NFS4/8/12--Supra) have been designed to comply with EN 54 part 2/4:1997 requirements.
This panel complies with the European low voltage directive 73/23/EEC (and the amending Directive 93/68/EEC), by the application of the safety standard
EN 60950.
The panel complies with the essential protection requirements of the EMC directive 89/336/EEC and the amending directives 92/31/EEC and 93/68/EEC, by the
application of de EN 50081-1, (emissions) and EN 50130-4, (immunity).
Mechanical specifications:
Box:
Enclosure and door: ABS V0.
Chassis: Galvanized and lacquered steel sheet.
Dimensions (mm):
350 (h) x 380 (w) x 125 (d)
Approx. Weight:
4 kg (without batteries)
Environmental specifications:
Operating
Temperature:
-5ºC a +45ºC, (recommended: +5ºC a 35ºC)
Operating Humidity:
5% a 95% R.H.
Height above sea level: Maximum 2000 m
Panel sealing:
IP 30 (EN 60529)
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
Electrical specifications:
Fuses:
Main fuse:
F 4A L 250V
Battery fuse:
F 2A L 250V
Sounders fuse:
2 x 250mA (electronic)
24V Aux.:
2 x 250mA (electronic)
Power Supply:
Mains supply:
230V~ (ac) ±15%, 50/ 60Hz, 65W (2,4A.)
Output Voltage:
29.4Vdc +/-7%
Output Current:
2.4A (Maximum load external circuits 2A:
Zones, Sounders, and 24V Aux.)
Battery Charger:
Charger Voltage:
27.3V at 20°C (temperature compensated)
Charger Current:
300mA */-10%