CHECK GAS TYPE
Use only the correct type of gas (natural or propane/LP). If your gas
supply is not the correct gas type, do not install fireplace. See dealer
where you purchased your fireplace for proper gas type fireplace or
to purchase gas conversion kit (see Accessories, page 30).
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNING: A qualified service person must con-
nect fireplace to gas supply. Follow all local codes.
CAUTION: For propane/LP units, never connect fire-
place directly to the propane/LP supply. This fireplace
requires an external regulator (not supplied). Install the
external regulator between the fireplace and propane/
LP supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with gas connector (if allowed by local
codes)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the equipment shutoff
valve from your retailer.
For propane/LP connection only, installer must supply an external
regulator. External regulator will reduce incoming gas pressure.
You must reduce incoming gas pressure to between 11" and 14" of
water. If you do not reduce incoming gas pressure, fireplace regula-
tor damage could occur. Install external regulator with vent pointing
down as shown in Figure 19. Pointing vent down protects it from
freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in cer-
tain areas. Check your local codes. Use pipe of 1/2"
diameter or greater to allow proper gas volume to
fireplace. If pipe is too small, undue loss of volume
will occur.
Installation must include an equipment shutoff valve, union and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from fireplace (see Figure 20).
IMPORTANT: Install main gas valve (equipment shutoff valve) in an
accessible location. The main gas valve is for turning on or shutting
off gas to appliance.
126741-01C

FIREPLACE INSTALLATION

Propane/LP Supply Tank
Figure 19 - External Regulator with Vent Pointing Down
Equipment Shutoff Valve
with 1/8" NPT Tap*
Approved
Flexible
Gas Line
* The equipment shutoff valve may be sup-
plied with the appliance or you can purchase
it from your retailer.
Superiorfireplaces.US.com
(Propane/LP Only)
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)
3" Minimum
Cap Pipe Tee Joint
Nipple
Sediment Trap/Drip Leg
Figure 20 - Gas Connection
External
Regulator
with Vent
Pointing
Down
13