Hitachi RPI-0.8FSG1 Service Manual page 88

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

TROUBLESHOOTING
Alarm
Code
# This alarm code appears when one of the following alarms occurs three times within 6 hours, which
may result in serious compressor damages, if the outdoor unit is continuously operated without
removing the cause.
Alarm Code:
These alarms are able to be checked by the CHECK Mode 1. Follow the action indicated in each
alarm chart.
These alarms are cleared only by turning OFF the main power switch to the system. However,
careful attention is required before starting, since there is a possibility which will result in
serious damages to the compressors.
1-78
Content of Abnormality
02
Tripping of Protection Device in Outdoor Unit
07
Decrease in Discharge Gas Superheat
08
Increase in Discharge Gas Temperature
39
Abnormality of Running Current at Constant Comp.
43
Pressure Ratio Decrease Protection Activating
44
Low Pressure Increase Protection Activating
45
High Pressure Increase Protection Activating
46
High Pressure Decrease Protection Activating
47
Low Pressure Decrease Protection Activating
Compressor Protection