Hitachi RPI-0.8FSG1 Service Manual page 85

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Alarm
Code
G "RUN" light flickers and "ALARM" is indicated on the remote control switch.
G The unit No., alarm code and the unit code is alternately indicated on the set temperature section,
and the unit No. and alarm code are indicated on the display of the outdoor unit PCB.
# This alarm is indicated when the revolution pulse output from the fan motor is 10rpm or less and the
reverse revolution signal is detected. The fan motor is stopped once, and restarted after 10 seconds.
It occurs more than 10 times in 30 minutes, this alarm is indicated. The abnormality occurs when the
fan motor is stopped.
Restart operation.
Does the motor run?
Does the fan stop by the
foreign matter?
Check to remove the connector CN14 on PCB1 and CN201, CN203, CN206
and CN207 on ISPM and CN15 and CN110 of trunk connector.
Are the connectors abnormal?
Replace the fan motor.
Restart operation.
Does the motor run?
Yes
No
Alarm code is not indicated.
Yes
No
Faulty
Good
Restart operation.
Does the motor run?
Yes
No
Alarm code is not indicated.
Abnormality of Fan Motor Protection
(Only 24 and 30HP 220V/60Hz)
Yes
No
In the case that the fan motor does not run
even the PCB is replaced, replace ISPM.
TROUBLESHOOTING
This alarm is indicated due to
detected overcurrent by the
contrary wind. This is normal.
Remove the foreign matter.
Connect it correctly.
This is normal.
This is normal.
Replace the PCB or
the fan controller.
1-75