Hitachi RPI-0.8FSG1 Service Manual page 128

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

TROUBLESHOOTING
(6) Checking of Electrical Coil Parts
Name of Parts
Fan Motor for Indoor Unit
for RPI-0.8FSG1, 1.0FSG1,
1.5FSG1
Fan Motor for Indoor Unit
for RPI-2.0FSG1, 2.5FSG1
Fan Motor for Indoor Unit
for RPI-3.0FSG1, 4.0FSG1
Fan Motor for Indoor Unit
for RPI-5.0FSG1
Fan Motor for Indoor Unit
for RCI-1.0 to 3.0FSG2
Fan Motor for Indoor Unit
for RCI-4.0FSG2, 5.0FSG2
Fan Motor for Indoor Unit
for RCD-1.0 to 2.0FSG1
Fan Motor for Indoor Unit
for RCD-2.5FSG1, 3.0FSG1
Fan Motor for Indoor Unit
for RCD-4.0FSG1
Fan Motor for Indoor Unit
for RCD-5.0FSG1
1-118
Model
Electrical Wiring Diagram
SF-200-60-4U
60W
SF-200-75-4U
1
75W
SF-200-290-4RC
3
290W
SF-200-290-4RB
290W
SIC-72FV-D856
56W
SIC-81F-D8108
108W
CCC6719AH
35W
3
CCC6720AH
55W
CCC6719BH
CCC6719CH
35W x 2
2
CCC6720BH
CCC6720CH
55W x 2
5
DC Motor
P
5
1
P
3
1
Resistance
Wiring No.
(Ω)
BL "1" - "3" R
21.1+10%
R "3" - "5" W
32.2+10%
o
at 20
C
BL "1" - "3" R
R "3" - "5" W
BL "1" - "3" R
5.06+10%
R "3" - "5" W
6.61+10%
o
at 20
C
BL "1" - "3" R
R "3" - "5" W
-
-
-
-
BL "1" - "3" R
159.0+10%
R "3" - "5" W
92.0+10%
o
at 20
C
BL "1" - "3" R
70.9+10%
R "3" - "5" W
51.7+10%
o
at 20
C
BL "1" - "2" R
159.0+10%
R "2" - "3" W
92.0+10%
o
at 20
C
BL "1" - "2" R
70.9+10%
R "2" - "3" W
51.7+10%
o
at 20
C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents