Hitachi RPI-0.8FSG1 Service Manual page 346

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

OPTIONAL FUNCTION
(4.4 Remote Control Switch)
Hi Speed at Heating
15
C6
Thermo-OFF
Canceling of
Enforced 3 Minutes
16
C7
Minimum Operation Time
of Compressor
Thermistor of
17
C8
Remote Control Switch
18
C9
Not Prepared
19
CA
Not Prepared
Selection of
20
Cb
Forced Stoppage Logic
21
CC
Not Prepared
22
d1
Power Supply ON/OFF 1
23
d2
Not Prepared
24
d3
Power Supply ON/OFF 2
25
E1
Ventilation Mode
26
E2
Increasing Supply Air Volume
27
E3
Not Prepared
28
E4
Precooling/Preheating Period
29
E5
Not Prepared
Automatic Setting for
30
F1
OFF Timer
Remote Control
31
F2
Main-Sub Setting
NOTES:
1. (*1): This function is applicable for RCI and RCD models. In case of RPI-0.8 to 5.0FSG1 series,
"Hi Speed 1" is "High External Pressure Setting" and "Hi Speed 2" is "Low External Pressure Setting".
2. As for the optional functions with " X " at the individual setting, only when the "All Rooms" is selected to set
the optional function, the setting condition can be changed.
3. The items "C1" and "C3" are not available. Do not change the setting condition "00".
4. For the models RPF(I)-FSG(E), RPI-8, 10HP, RPC-FSG1 (Before Alternation) and RPK-FSGM (Before
Alternation), only the function setting of No.1 to No.9, No.17 and No.30 are available.
(No.17 is settable "01" only.)
4-42
00
Not Available
01
Available
00
Not Available
01
Available
00
Control by Indoor Suction Thermistor
01
Control by Thermistor of Remote Control Switch
02
Control by Average Value of Indoor Suction
Thermistor and Thermistor of Remote Control
Switch
00
Forced Stoppage Input

01
Forced Stoppage Input
00
Not Available
01
Available
00
Not Available
01
Available
00
Automatic Ventilation
01
Ventilation by Total Heat Exchanger
02
Bypass Ventilation (No Total Heat Exchanging)
00
Not Available
01
Available
00
Standard
01
30 minutes
02
60 minutes
00
No Function
01
OFF Timer by 1 hour
02
OFF Timer by 2 hours

M
23
OFF Timer by 23 hours
24
OFF Timer by 24 hours
00
Main

01
Sub
A Contact
B Contact

Hide quick links: