(17) Remote Control Thermistor
This function is utilized to control the unit by the built-in thermistor of the remote control switch
(remote control thermistor) instead of the thermistor for suction air.
Set this function at "01" or "02" when utilizing this function.
However, even when this function is set at "01" or "02", the detecting temperature is abnormal due to
the failure of the remote control thermistor, etc., the thermistor to be used is changed to the
thermistor for suction air of the indoor unit automatically.
(18) Not Prepared
(19) Not Prepared
(20) Selection of Forced Stoppage Logic
This function is utilized to select the logic of the contact for forced stoppage signal input.
The setting condition and the logic of the contact are as shown below.
(21) Not Prepared
(22) Power Supply ON/OFF 1 (Automatic Operation When Power Supply ON for the models of RPI-0.8 to
5.0FSG1, RCI-FSG2, RCD-FSG1 and RPC-FSG1 (After Alteration). In case of other models, refer to
the item 4.1.2.)
This function is utilized to start and stop the unit according to the power supply ON/OFF.
When this function is utilized in the condition that there is no person to operate the unit, make the
system with monitoring for disaster prevention.
NOTE:
The unit is started and stopped according to the power supply ON/OFF due to the power failure.
When the power failure is occurred during stoppage by the remote control switch operation, the unit is
started again automatically after the power supply is recovered.
(23) Not Prepared
(24) Power Supply ON/OFF 2 (Restarting Function After Power Failure for the models of RPI-0.8 to
5.0FSG1, RCI-FSG2, RCD-FSG1 and RPC-FSG1 (After Alteration). In case of other models, refer to
the item 4.1.3.)
This function is utilized to start the unit operation again automatically when the power supply is
recovered after the power failure over 2 seconds.
The standard unit is started operation again automatically with all the same operating conditions such
as operation mode, etc. in case of the power failure within 2 seconds.
(The compressor is started operation again after three minutes guard in addition to 2 seconds power
failure as a maximum.)
NOTE:
In case of the power failure during the unit stoppage, the unit is stopped after recovering the power supply.
(25) Ventilation Mode (Total Heat Exchange Model)
This function is utilized to set the ventilation mode of the total heat exchanger.
The setting condition and the ventilation mode are as shown below.
Setting Condition
00
01
02
Ventilation Mode
Automatic Ventilation
Total Heat Exchanging
Ventilation
Bypass Ventilation
Contents
Selecting effective ventilation mode (Total Heat
Exchanging Ventilation or Bypass Ventilation)
for energy saving by detecting the temperature
difference between the outdoor temperature and
the room temperature.
The heat exchanging is performed continuously
when the total heat exchanger is operated.
The heat exchanging is not performed continuously
when the total heat exchanger is operated.
OPTIONAL FUNCTION
(4.4 Remote Control Switch)
4-45