INSTALLATION
The minimum components required for a basic horizontal
termination are:
1
Horizontal Termination Cap
1
90
Elbow
o
1
Rigid Pipe Adaptor (510-994)
1
Wall Thimble
1
Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl siding standoff, to
create a level surface to mount the vent terminal. The Terminal
must not be recessed into siding. Measure the wall thickness
including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl
siding), measure to outside surface of wall without siding and
add 51mm.
Flat Wall Installation
Wall Thickness
(inches)
4" - 5-1/2"
7" - 8-1/2"
10" - 11-1/2"
9" - 14-1/2'
15" - 23-1/2"
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCap
Riser is acceptable with all systems.
This product has been evaluated by Intertek
for using a Rigid Pipe Adaptor in conjunction
with Duravent Direct-Vent, Selkirk Direct-Temp,
Ameri Vent Direct Venting, ICC Excel Direct
and Security Secure Vent systems. Use of
these systems with the Rigid Pipe adaptor is
deemed acceptable and does not affect the
Intertek WHI listing of components.
The FPI AstroCap
TM
and FPI Riser Vent terminal are certified for installations using FPI venting systems as well as Simpson Dura-Vent
can Metal Products Ameri Vent Direct Vent, Security Secure Vent
Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
20

HORIZONTAL TERMINATIONS

RIGID PIPE 4" X 6-5/8
Vent Length Required
(inches)
6"
9"
12"
11" - 14-5/8" Adj. Pipe
17" - 24" Adj. Pipe
and FPI
TM
" (
102MM X 175MM)
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
, ICC Excel, Selkirk Direct-Temp. AstroCap
®
Termination Cap
Vinyl Siding
Standoff (Optional)
Wall Thimble
Adj.Pipe Length
90
o
Elbow
Rigid Pipe Adapter
®
Direct Vent, Ameri-
is a proprietary trademark of FPI Fireplace
TM
Regency GF900C Gas Fireplace
Horizontal