Other Functions; Led Display; Operation Lamp; Condensate Pump - York YKHC 18 Service Manual

Cassette ykhc 18 to 48
Table of Contents

Advertisement

4. Other Functions

4.1 LED Display

Operation lamp, timer lamp, defrosting/pre-heating lamp, and water level alarm lamp.

4.1.1 Operation Lamp

When the operation is recovering, it will blink at 1 Hz.
After the unit is on, the lamp will keep on.
After the unit is off, the lamp will be off.
When the unit is switched over from manual cooling to remote control, the lamp will be off.
4.1.2 Timer Lamp
During timer operation, it will be on.
4.1.3 Defrosting/Pre-Heating Lamp
When heat pump model performs defrosting or anti-cold air, it will be on.
4.1.4 Water Level Alarm Lamp
When water level is above the alarm level, it will blink at 5Hz.
4.2 Timer
Refer to remote controller manual for detail operation.
Note: The timer is valid for one operation of the A/C.
4.3 Louver Action
Closed angle at energized
°
55
The swing angle is between 15° and-15° with 15°being its center .

4.4 Condensate Pump

4.4.1 The action of the water pump is controlled by water level switch.
4.4.2 Control procedures (check water level every 5 seconds )
4.4.2.1 When entering cooling mode, dehumidifying mode or forced cooling mode, condenser starts at once and
operates continue until the above modes stop.
4.4.2.2 Under stand-by, heating or fan mode, if the water level in water receiver rises to the position of the water
switch, the controller will make LED flashing to give warning signal, and at the same time forces compressor to
stop and the drain pump start. The water level will be checked continuously. If the water level falls to warning
water level, the warning signal will disappear( the drain pump delay 1 minute to be off), compressor starts again(3
minutes protection takes priority), and operation recovers according to former setting mode. On the other wise,
after 3 minutes, the whole unit stops(including drain pump) and warning signal can"t disappear. It can"t recover
unless out of power.
Heating
Cooling or dehumidifying
°
30
18
°
30
Swing range
°
0-30