Specifications; Ups Specifications; Table 6 - Liebert GXT2-6000RTL630 User Manual

Liebert uninterruptible power supply owner's manual
Table of Contents

Advertisement

13.0 S
PECIFICATIONS

Table 6

UPS specifications

Model Number
Dimensions, in. (mm)
Weight, lb (kg)
Input AC Parameters
Nominal Operating Frequency
User Configurable VAC
Operating Voltage Range Without
Maximum Allowable VAC
Input Frequency Without Battery
Input Power Connection
Output AC Parameters
Bypass Protection Limits
Disable Bypass operation
Re-enable Bypass operation
Disable Bypass operation
Environmental
Operating Temperature
Agency
Radiated Susceptibility
Electrical Fast Transient
Model Rating
Unit, W x D x H
Shipping, W x D x H
Unit
Shipping
Factory Default VAC
Battery Operation
Operation
Factory Default VAC
Output Connections
Frequency
Waveform
Main Mode
Overload
Storage Temperature
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
Safety
EMI/EMC
ESD
Surge Immunity
Transportation
GXT2-6000RTL630
6000VA/4200W
8.7 x 21.5 x 16.9 (221 x 547 x 430)
22.0 x 27.2 x 19.7 (560 x 690 x 500)
50 or 60Hz (Factory Default = 60)
208/220/230/240VAC
(May be modified using configuration program)
176 – 276VAC
L6-30P Plug (on PD-L630 power distribution box)
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
50Hz or 60Hz, Nominal
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
If input voltage exceeds ±15% of the nominal voltage
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
32°F to 104° F (0°C to 40°C)
5°F to 122° F (-15°C to 50°C)
0-95% non-condensing
Up to 6600 ft (2000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
<55 dBA, at 3 ft. (1m) from the rear
<50 dBA, at 3 ft. (1m) from the front or sides
UL, C-UL Listed to UL1778
FCC Class B
EN61000-4-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-5, Level 3, Criteria A
ISTA Procedure 1B
36
57.2 (26)
81.5 (37)
208VAC
276VAC
40 - 70Hz
208VAC
Sinewave

Specifications

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents