Status; Communication Interfaces - Liebert 30-130kVA Operation And Maintenance Manual

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Table 7
Alarms, functions, and corrective actions (continued)
Actual
Alarm/fault
Name
Displayed
Description
On Front
of Alarm/
Panel
Fault
Input Contact
Input Contact
#4
#4
Input Contact
Input Contact
#5
#5
Input Contact
Input Contact
#6
#6
Input Contact
Input Contact
#7
#7
Input Contact
Input Contact
#8
#8
NOTE
There are 8 alarms on the Remote Alarm Status Panel. See 3.5.3 - Remote Alarm Status
Panel
3.4.3

Status

Status conditions give the Operator additional knowledge about UPS operation. Some are indicated
on the Mimic Display screen by a text message while others are depicted graphically.
The following status messages may appear in the Operator display.
• Static Switch Connected. The static switch is connected (the disconnect switches are closed - ON)
and is ready to provide a current path from the bypass input to the load.
• Static Switch Disconnected. The static switch is disconnected (the disconnect switches are open -
OFF) for maintenance procedures.
• OK to Transfer. The UPS system voltage, frequency, and phase match the bypass line. This
means that a transfer between the bypass line and the UPS is permitted.
• Not OK to Transfer. Either the UPS or bypass voltage, frequency, or phase is not within the spec-
ified limits or the static bypass switch is not available. Therefore, manually-initiated transfer
between the bypass line and the UPS is not permitted. Emergency or overload transfer to bypass
may still be available provided the "Static Switch Unable" alarm is not indicating.
• Time to Overload Transfer. During an overload condition, the time remaining before transfer (in
seconds) is displayed at the bottom of the load block.
3.5

Communication Interfaces

The Npower UPS can be configured with various communication ports to assist the Operator in moni-
toring the UPS system.
Fault
Or
Latch
Dial
Freeze
Alarm
Mask
Mask
Mask
Alarm
YES
YES
Alarm
YES
YES
Alarm
YES
YES
Alarm
YES
YES
Alarm
YES
YES
Event Log
Mask
Meaning and Corrective Action(s)
The System has been notified from the OC-
DI option that a customer alarm has been
NO
YES
activated. The system will substitute user-
defined text when displaying these alarms.
The System has been notified from the OC-
DI option that a customer alarm has been
NO
YES
activated. The system will substitute user-
defined text when displaying these alarms.
The System has been notified from the OC-
DI option that a customer alarm has been
NO
YES
activated. The system will substitute user-
defined text when displaying these alarms.
The System has been notified from the OC-
DI option that a customer alarm has been
NO
YES
activated. The system will substitute user-
defined text when displaying these alarms.
The System has been notified from the OC-
DI option that a customer alarm has been
NO
YES
activated. The system will substitute user-
defined text when displaying these alarms.
88
Operation