Figure 28 External maintenance bypass switch, single-input UPS

UPS Input
The table below summarizes the External Maintenance Bypass switch positions and actions.
Table 3
External maintenance bypass switch positions and actions
Switch position
Maintenance (Service)
Test (Bypass)
On Line (Transition)
On Line (Normal)
When the External Maintenance Bypass switch is in Bypass or Maintenance position, the UPSC will
assert the bypass contactor close signal and the output contactor open signal. It will also turn on the
SBS. Automatic Retransfer operations will be disabled.
If the External Maintenance Bypass switch rotates from the Bypass or Maintenance to the Normal
position, then the UPSC will keep the bypass in the ON state, thus keeping the critical bus powered
via the bypass source. The user will be able to issue a "Manual Transfer to Inverter" command pro-
vided the retransfer conditions are satisfied. The user can also issue a shutdown or a start command.
If the External Maintenance Bypass switch rotates from the Normal to the Bypass or Maintenance
position, the UPSC will assert the bypass contactor close signal and the output contactor open signal.
It will also turn on the SBS. Automatic Retransfer operations will be disabled.
S1-B
S1-A
IMBS
SBS
Rect
INV
Battery
S1-A
S1-B
Open
Closed
Closed
Closed
Closed
Closed
Closed
Open
31
Critical load
S1-C
S1-C
AUX
Open
Open
Open
Open
Closed
Open
Closed
Closed
Operation