Table 7 Alarms, Functions, And Corrective Actions - Liebert 30-130kVA Operation And Maintenance Manual

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Alarm Messages
The alarm message area displays the alarm conditions that are present within the UPS system. The
table below shows the default values of masks for each alarm/fault, the meaning of the Alarm and
possible corrective actions.
The following information applies to the table.
1. Latch Masks, Dial Masks and unshaded Event log masks may be changed by the user. The user
may not change any Freeze Masks.
2. The default alarm names for Input Contact 1 through Input Contact 8 can be modified by the
user.
Table 7
Alarms, functions, and corrective actions
Actual
Alarm/fault
Name
Displayed
Description
On Front
of Alarm/
Panel
Fault
Battery Fuse
Battery Fuse
Fail
Fail
Battery Low
Battery Low
xfer
Transfer
DC Ov
DC Overvolt
Transient
Transient
Inp Phase
Input Phase
Rot Error
Rotation Error
Rectifier Fuse
Rectifier Fuse
Fail
Fail
Fault
Or
Latch
Dial
Freeze
Alarm
Mask
Mask
Mask
Fault
YES
YES
Fault
YES
YES
Fault
YES
YES
Fault
NO
NO
Fault
YES
YES
Event Log
Mask
Meaning and Corrective Action(s)
Control Logic has determined that the
battery breaker(s) is closed and the battery
fuse has been open for 10 seconds or
NO
YES
longer. Battery back-up is no longer
available. Liebert Global Services should
be called immediately.
Control Logic has determined that the
battery breaker(s) is closed and the battery
voltage has dropped below the End of
Discharge limit. The UPS will transfer to
bypass. If the transfer is successful, the
UPS will be shut down. If the transfer was
YES
YES
unsuccessful, logic will attempt to complete
a System Shutdown before control power is
lost. Verify that input power is now available
and restart the UPS following the
instructions in this manual. If the system
fails to restart properly contact Liebert
Global Services.
DC bus voltage is 15% or more over the
nominal DC Bus Voltage. The UPS will
NO
YES
transfer the load to Bypass and will shut
down and isolate the UPS Module. Contact
Liebert Global Services immediately
The power conductors on the Input line are
not wired to the UPS in the required
sequence. This alarm should appear only
during initial start-up or after a repair to the
NO
YES
source power system. Disconnect power
from the Input line and correct the wiring.
Liebert Global Services must be present
during initial start-up of your UPS System.
At least one fuse has opened. The UPS
automatically transfers the critical load to
the bypass line. Contactors trip open to
NO
YES
shut down and isolate the UPS module.
Contact Liebert Global Services
immediately. Do not attempt to reset the
circuit breakers.